TECHNICAL DETAILS
Description
DH55AX DH55TTW
Model
30AP
30AXP
DH33A
DH33AX DH33TTW
50AP
50AXP
DH55A
2.5
l/h
1.25
1.25
1.25
1.25
1.25
2.5
2.5
2.5
2.5
Dehumidification
60.0
l/d
30.0
30.0
30.0
30.0
30.0
60.0
60.0
60.0
60.0
Dehumidification
n/a
kW
2.0
2.0
n/a
n/a
n/a
4.0
4.0
n/a
n/a
Elect Heat Output
5.0
kW
n/a
n/a
3.0
3.0
3.0
n/a
n/a
5.0
5.0
LPHW Heat Output
5.0
l/min
n/a
n/a
5.0
5.0
5.0
n/a
n/a
5.0
5.0
LPHW Flow Rate
1.8
m hd
n/a
n/a
1.1
1.1
1.1
n/a
n/a
1.8
1.8
LPHW Pressure Drop
15
mm
n/a
n/a
15
15
15
n/a
n/a
15
15
Pipe Connections LPHW
15
mm
15
15
15
15
15
15
15
15
15
Condensate Drain
240 Volts / 50 Hz
Electrical Supply
13.0
AMP
20.0
20.0
10.0
10.0
10.0
32.0
32.0
13.0
13.0
Fuse
5.6
AMP
12.1
12.1
3.4
3.4
3.4
23.0
23.0
5.6
5.6
Nominal Running
1.2
kW
2.8
2.8
0.75
0.75
0.75
5.3
5.3
1.2
1.2
Power Consumed
30.0
AMP
15.8
15.8
15.8
15.8
15.8
30.0
30.0
30.0
30.0
Compressor LRA
47
dB(A)
52
52
48
48
46
54
54
48
48
Noise Level @ 3m
Dimensions:
1300
mm
780
780
780
780
875
1245
1245
1245
1245
Width
290
mm
250
250
250
250
290
250
250
250
250
Depth
745
mm
655
655
653
653
745
655
655
653
653
Height
70
kg
40
40
40
40
48
60
60
60
60
Weight
·
LPHW = Low pressure hot water
·
These performance figures are based on air at
30 degree C and 60% RH and pool water at
·
Humidistat adjustable from 20% to
28 degree C with boiler water at 80 degree C.
80% RH.
·
Vaporex units are covered by a full two year
·
Minimum air temperature on standard
parts and labour warranty.
models is 15 degrees C, the defrost models
will operate down to 0 degrees C.
·
All Vaporex units are R407C ozone friendly
refrigerant
·
Fuses should be motor rated.
·
Manufactured in the UK.
·
TTW models are supplied with inlet and
outlet grilles. (C/W sleeves)